Detail Product
LBS Motorized
Desain LBS ( PT.ines – Techpro)
The Load Break Switch that we make has the TP-250P type, with a Pole Mounted model and is isolated using SF6 gas. TP-250P is installed on a medium voltage distribution network system and is useful for isolating interference so that interference does not spread. The TP-250P is installed by connecting to the FRTU so that system integration can be carried out which functions as remote control, telemetering, and telesignaling in detecting errors or disturbances.

SF6 Gas Load Break Switch 24kV 630A 16kA
The TP-250P has an operating mechanism, namely three CTs for each phase, and 6 VT sensors for each phase on each side. Has an indicator to check the status of SF6 gas (low or not), so this device has high operational stability. This type also has a mechanical handle to close and open the switch and a position indicator to show the contact position.
There is a manual locking lever (handle lock) that functions to prevent or prohibit mechanical control (close/open) either remotely or locally, which can only be controlled by the user to block the operation. So that all control and system operation can be protected.
Spesifikasi

Specification | Unit | TP250-P6A | |
---|---|---|---|
Rated Voltage | kV | 24 | |
Rated Current | A | 630 | |
Rated Frequency | Hz | 50 | |
Rated Short Time Current | kA/sec,rms | 16 | |
Rated Making Current | kA/time,peak | 40 | |
Withstand Voltage | Power Frequency | kV/min | 50 |
Lightning Impulse | kV, 1.2 x 50 µs | 125 | |
No. of Operation | at Rated Current | Times (rated voltage) | 200 |
at Rated Making Current | 5 | ||
Mechanical | 5000 | ||
Rated Frequency | VAC/VDC | 220/224 | |
Rated Gas Pressure | Normal | kg/cm².G @20°C | 0.7 |
Minimum Lock | 0.3 | ||
Main body weight | kg | 220 | |
Applied Standards | IEC 60265-1 | ||
IEC 62271-103 |